Smoke Detector
Model: HM-613PC-4
This product named Photoelectric smoke detector(hereinafter called detector) detects the smoke by a couple of infrared diodes. The principle of detecting is granule in the smoke can reflect infrared light. Infrared diodes are placed in the special chamber. The chamber can shield external light, but doesn't affect the smoke into it. While there is no smoke, thediode can receive very weak infrared light. When the smoke entering the chamber, diode can receive more and more light, and the detector can give out alarm signal when the smoke attains the certain density. In order to reduce the interferenceand lower power consumption, the emitting circuit adopts the pulse signal. The product in accordance with the networkingapproach is divided into 2- wire and 4-wire detectors.

This product named Photoelectric smoke detector(hereinafter called detector) detects the smoke by a couple of infrared diodes. The principle of detecting is granule in the smoke can reflect infrared light. Infrared diodes are placed in the special chamber. The chamber can shield external light, but doesn't affect the smoke into it. While there is no smoke, the
diode can receive very weak infrared light. When the smoke entering the chamber, diode can receive more and more light, and the detector can give out alarm signal when the smoke attains the certain density. In order to reduce the interference
and lower power consumption, the emitting circuit adopts the pulse signal. The product in accordance with the networking
approach is divided into 2- wire and 4-wire detectors.
●STRONG ADAPTABILITY FOR CIRCUMSTANCE
●SMT DESIGN, HIGH STABILITY
●10-30VDC WIDE VOLTAGE OPERATING RANGE
●LOW STANDBY CUR R ENT
●POWER SUPPLY NON-POLARIZED INPUT
●TWINLED FOR 360°VISUAL
●FL ASHING LED POWER INDICATOR
●REMOTE LED INDICATOR OUTPUT(2- WIRE)
●METAL SHIELD, ANTI-ELECTROMAGNETIC INTERFER ENCE
Working voltage: DC10 ~ 30V
Static current: 4mA (Relay normal open), 13mA (relay normal close)
Alarm current: 19mA (relay normal open), 9mA (relay normal close)
Alarm indication: red LED
Smoke sensitivity: 0.2dB / m (± 0.1dB / m)
Working Temperature : -10 ℃ ~ + 50 ℃
Environmental humidity:95% RH
Alarm output: relay output (normal open / normal closel)
Relay contact capacity: 0.1A, DC28V
Protected area: 60-80 square meters
Related Products
-
KNX Tile Series 8 Buttons Smart Panel 2.1
Products Current Page: Home Products KNX Tile Series Featuring cross-protocol compatibility, a comprehensive product portfolio, and globally adaptable installation, it meets diverse project demands with ease. Every detail — from precision engineering to refined finishes — is crafted to enhance reliability and elevate the user experience Flexible Combinations, Complete Solutions Tile Series offers over 30 […]
-